FEATURES
- High quality Taut Band movement.
- Three insulation test voltages(DC) : 250V, 500V, 1000V.
- Two continuity test on “low ohms” : 3Ω & 500Ω.
- AC voltmeter with linear scale up to 600 Vac.
- 200mA short circuit current for continuity.
- 1mA test current on insulation test at nominal voltage.
- Automatic discharge of capacitive and inductive circuit with charge stored in the circuit under test.
- Live warning and display of external voltage presence.
- Fuse, air gap, crowbar and overload protected.
- On line battery monitoring shows if battery is ok.
- Manual zero ohm adjustment.
- Low battery consumption.
- Mirror scale.
- Push and turn locking switch for continuous and hand free testing.
- Supplied with high quality test leads.
- BS 16th edition.
SPECIFICATIONS
Insulation Resistance
Test voltage (DC V) |
250V / 500V / 1000V |
---|---|
Output voltage on open circuit | Rated test voltage +10% |
Measuring ranges | 0-100MΩ / 0-200MΩ / 0-400MΩ |
Mid-scale value | 1MΩ / 2MΩ / 4MΩ |
Scale multiplier | ×1/2 / ×1 / ×2 |
Accuracy | ± 5% of full scale |
Output short-circuit current | Approx. 1.3mA |
Continuity
Measuring ranges | 3Ω / 500Ω |
---|---|
zero Ω adjustment by knob | |
Output short- circuit current | ≥ 200 mA |
Accuracy | ± 1.5% of scale length |
AC Voltage
Range | 0-600V AC |
---|---|
Accuracy | ± 3% of scale length |
General
Voltage warning | Warning light circuit live lit From 90Vdc / 70Vac, Buzzer beep from 24V ac/dc |
---|---|
Dimensions | 163(L) × 122(W) × 62(D)mm |
Weight (battery included) |
Approx. 553.5g |
Power source | 1.5V (AA) × 6 |
Safety standard | EN 61010-1 CAT III 600V EN 61326-1 |