FEATURES
- High quality Taut Band movement.
- Capable of measuring earth resistance and earth voltage.
- 2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.
- The test leads are supplied as standard accessories for simplified two-wire measuring system.
- Battery operated.
- Battery check function.
- Calibration performed with supplied test leads.
SPECIFICATIONS
Measuring ranges | Earth resistance 0-10Ω / 0-100Ω / 0-1000Ω Earth voltage 0-30 Vac (40-500Hz) |
---|---|
Accuracy | Earth resistance ±3% of full scale Earth voltage ±2.5% of full scale |
Measuring system | Earth resistance by constant current inverter 820 Hz, 2mA approx |
Open circuit indication | LED will be unlit |
Dimensions | 205(L) × 90(W) × 55(D)mm |
Weight (battery included) |
Approx. 514g |
Power source | 1.5V (AA) × 6 |
Safety standards | EN 61010-1 CAT III 30V EN 61326-1 |
Feedback list