FEATURES
- Microprocessor-controlled.
- Telecommunication test voltage : 50V and 100V.
- Large range of insulation test voltages: 50, 100, 125, 250, 500, 1000V.
- Mov / protection devices test.
- Gas Arrester function.
- Automatic voltmeter AC/DC at Start/Reset.
- Test ON-OFF.
- Battery test.
- Safety voltmeter before each test.
- Auto-discharge on all test and all ranges.
- Battery test at Switch ON-TEST.
- Smart hold & Stop on voltmeter AC/DC.
- eads AUTO-NULL Key.
- Test Auto-stop.
- Auto range.
- Ener-Save™.
SPECIFICATIONS
Insulation Resistance
Test voltage (DC) and Measuring ranges | 50V / 0.1MΩ~400MΩ 100V / 0.1MΩ~800MΩ 125V / 0.1MΩ~1GΩ 250V / 0.2M~2GΩ 500V / 0.2MΩ~4GΩ 1000V / 0.2M~8GΩ |
---|---|
Output voltage @ 1mA | Rated test Voltage +10% |
Accuracy | 0.1MΩ~4GΩ : ±3%rdg 4GΩ~8GΩ : ±5%rdg |
Nominal voltage rated | 1mA |
Short circuit current | 1.2mA |
Polarization index(PI) | |
Dielectric absorption ratio (DAR) |
Continuity
Ranges | 0.01~100Ω / 100 ~300Ω / 300~1999Ω |
---|---|
Accuracy | 0.01~100Ω : ±1.0%rdg 100~300Ω : ±1.5%rdg 300~1999Ω : ±2.0%rdg |
Auto-null | up to 5Ω |
Buzzer | up to 3Ω |
Voltmeter
DC voltage | 0-950V |
---|---|
AC voltage | 0-700V |
Resolution | 1V |
Accuracy | ±1.5% rdg |
MOV Test & GAS Arrester Test
Measuring range | 5~1020 Vdc |
---|---|
Accuracy | ±(3%rdg + 2dgt) |
General
Fuse | 500mA 250V (5 × 20mm) HBC. Fast Blow |
---|---|
Display | LCD |
Operating temperature | 0°C to 40°C |
Storage temperature | -10°C to 50°C |
Dimensions | 250(L) × 190(W) × 110(D)mm |
Weight (battery included) |
Approx. 1460g |
Power source | 1.5V (AA) × 8 Alkaline batteries |
Safety standard | EN 61010-1 CAT III 600V EN 61326-1 |
Feedback list