FEATURES
- Microprocessor-controlled.
- Measures Insulation Resistance, voltage (AC-DC) measurements with automatic hold facility, diode, ohm, and continuity with a short circuit current of minimum 220mA.
- Auto-off function.
- Energy conservation feature.
- Ener-Save™ limit the test duration to about 10 Seconds.
- Quick Test and EnerSave™ are unique features. Both saves energy.
- No moving parts. All calibration are saved internally in a non volatile memory.
- Easy calibration at any facility around the world.
- Operates with rechargeable batteries, alkaline or low cost general purpose batteries.
- Low cost maintenance, calibration, and ownership.
- Complies to all the latest regulations, including UK.
SPECIFICATIONS
Insulation Test
| Test voltage (DC V) |
250V / 0.2M~2GΩ 500V / 0.2M-4GΩ 1000V / 0.2M-8GΩ |
|---|---|
| Output voltage @ 1mA | Rated test Voltage +10% Max |
| Accuracy |
0.2M~4GΩ : ±3%rdg 4GΩ~8GΩ : ±5%rdg |
| When voltage is constant, Current is limited at | 1.2mA |
| Short circuit current | 4mA Max. |
Continuity
| Measuring ranges | 0.01-1999Ω |
|---|---|
| Accuracy | 0.01-100Ω : ±1.0%rdg 100-300Ω : ±1.5%rdg 300-1999Ω : ±2.0%rdg |
| Short circuit current | >220mA |
| Open circuit voltage | 5V dc |
| Resolution | ±2 counts |
Voltmeter
| AC voltage (Auto) | 0-700V |
|---|---|
| DC voltage (Auto) | 0-950V |
| Accuracy | ±1.5% rdg |
| Resolution | ±1V |
Protections
| Over load | 700V (between all terminals) |
|---|---|
| Over voltage | Class III-700V towards ground |
| Fuse | 500mA 250V, (5 × 20mm), HBC, Fast Blow |
General
| Display | 2 lines × 16 characters LCD |
|---|---|
| Auto-null threshold | 5Ω |
| Buzzer threshold | 3Ω |
| Fast test | 10Sec |
| Long test | 60Sec |
| With PI and DAR test function | 10Min |
| Load battery test current | About 300mA |
| Operating temperature | 0°C to 40°C not in full sun |
| Storage temperature | -10°C to 50°C |
| Dimensions | 250(L) × 190(W) × 110(D)mm |
| Weight (battery included) |
Approx 1460g. |
| Power source | 1.5V(AA) × 8 |
| Safety standard | EN 61010-1 CAT III 600V EN 61326-1 |


Feedback list