FEATURES
- Microprocessor-controlled.
- 2Lines × 16 Characters LCD.
- Very low consumption.
- Suitable for industrial applications.
- Better than 3% accuracy (current).
- Menu-driven.
- Accurate digital readout of disconnection time.
- Accurate digital readout of disconnection sensitivity.
- Data hold function.
- Zero Crossing Circuitry permit testing at 0° or 180°.
- Disconnection Phase Polarity shown on LCD display.
- Auto off and off override.
- Polarity Trip indicator (Positive of Negative Phase).
SPECIFICATIONS
| Current settings | 0-999mAac / 50Hz | 
|---|---|
| Current selection | Knob | 
| Phase start selection 0° and 180° | Referenced to Earth Yes | 
| Over-temperature protection | Yes | 
| Phase polarity trip Indicator | Referenced to Earth Yes | 
| Operating voltage (L-E) | 110 Vac to 450 Vac | 
| Timer resolution | 1ms (Max. Time = 99.999s) | 
| Timer accuracy | 1ms ±1ms | 
| Current accuracy | ±1% ±1mA | 
| Current resolution | 1mA | 
| Voltmeter accuracy (50Hz) | 50-350 Vac = ±2%±1V 350-450 Vac = ±5%±1V | 
| Voltameter resolution | 1V | 
| Operating temperature | -5°C to 40°C | 
| Storage temperature | -10°C to 55°C | 
| Maximum current Specified at | 450 Vac/50Hz | 
| Dimensions | 170(L) × 165(W) × 92(D)mm | 
| Weight (battery included) | Approx. 1180g | 
| Power source | 1.5V (AA) × 8 | 
| Safety standard | EN 61010-1 CAT III 600V EN 61326-1 | 
 
						

 
 
Feedback list