FEATURES
- Microprocessor-controlled.
- Indicates phase rotation.
- Indicates phase presence.
- Tests for disconnection sensitivity.
- Indicates battery status.
- Tests for disconnection time.
- Measures voltage phase to earth.
- Select one of 3 Phase to test ELCB.
- Color-coded test leads.
- Phase presence indication from as low as 100Vac.
- Very low consumption.
- Fused earth leakage tester.
- ELCB works 50Vac to 330Vac 50Hz / 60Hz.
- Led indication of Voltage on ELCB.
- Phase rotation and presence does not require battery to indicate.
- EN 61010-1 CAT III 550V. EN 61326-1
SPECIFICATIONS
Determination of the Phase Presence
Nominal Voltage for Phase Presence Indication (the voltage required for the neon lamps L1, L2, L3 to lit up) | From 100Vac to 450Vac. |
---|---|
Frequency Range | From 10Hz to 400Hz. |
Determination of the Phases Rotary Field Direction
Direction (the voltage required to have the direction LEDs L1-L2-L3 or L2-L1-L3 to indicates) | From 100 to 450Vac. |
---|---|
Frequency Range | From 2Hz to 400Hz. |
Protection
Over Load | 550V(between all terminals) |
---|---|
Over Voltage | Class III - 450V towards ground. |
Earth Leakage
Current Settings | 999mAac / 50Hz-60Hz |
---|---|
Current Selection | Knob |
Phase Start Selection(*) | 0° and 180° |
Over-Temperature Protection(*) | Yes |
Phase Polarity Trip Indicator(*) | Yes |
Operating Voltage(L-E) | 220Vac to 317Vac |
(*)Referenced to Earth | |
Timer Resolution | 1ms(Max. Time = 99.99s) |
Timer Accuracy | 1ms ± 4ms |
Current Accuracy | ±3% ± 4mA |
Current Resolution | 1mA |
Voltmeter Accuracy(50Hz) | 50-350 Vac = ±3% ± 2V 350-550Vac = ±7% ± 3V |
Voltmeter Resolution | 1V |
Maximum Current Specified at 317Vac / 50Hz | |
Batteries | 1.5V "C" × 8 Alkaline batteries Bat OK Led = Vbat >9V |
Dimensions | 330(L) × 260(W) × 160(D)mm |
Weight | 3850g (batteries included) |
Operating temperature Range | 0°C to + 40°C |
Storage Temperature | -10°C to + 50°C |
Feedback list