FEATURES
- 9000 MF multi-function tester is a combination of insulation tester and earth resistance tester
- Insulation output voltage : 50V, 100V, 125V, 250V, 500V, 1000V
- 1mA test current on insulation test at nominal voltage
- Auto-detection AC/DC voltmeter
- Continuity short-circuit current > 200mA
- Continuity open circuit voltage > 4.1V
- PI and DAR indication
- Maximum insulation range 8GΩ ( 8000MΩ ) at 1000V
- Auto ranging on all insulation ranges
- Continuity range : 2000Ω and 200.0Ω (auto ranging )
- Auto power off
- Test frequency of earth resistance measurement : 128 Hz
- Earth resistance measurement for 3 ranges : 40Ω / 400Ω / 4kΩ
- Earth resistance resolution : 0.01Ω / 0.1Ω / 1Ω
- Earth voltage measurement : 400V
- Auto-null ( Relative mode ) function
- Backlight function
- Low battery
SPECIFICATIONS
Earth Resistance
Measuring ranges |
|
---|---|
Accuracy | ± (2.0%+3dgt) |
Insulation
Test voltage(DC V) | Ω | 1000V/500V | 250V/125V | 100V/50V |
---|---|---|---|---|
Measuring ranges | 2kΩ | 8GΩ/4GΩ | 2GΩ/1GΩ | 800/400MΩ |
Accuracy | ± (2.0% + 3dgt) | 0-4GΩ: ±(3.0% + 3dgt) 4-8GΩ: ±(5.0% + 3dgt) |
||
Output voltage on open circuit |
Rated test voltage +15% | |||
Short circuit terminal current |
>200mAdc | > 1mAdc | ||
AC voltage ranges | 30~600V ± (2.0% + 3dgt) | |||
Frequency ranges | 10~999Hz ± (2.0% + 3dgt) | |||
DC voltage ranges | 30~600V ± (2.0% + 3dgt) |
General
Protection fuse | 500mA / 600V , 5x20mm x 2 |
---|---|
Dimensions | 322(L) × 260(W) × 135(D)mm |
Weight (battery included) |
Approx. 3300g |
Power source | 1.5V "C" battery × 8 |
Safety standard | EN 61010-1 EN 61326-1 EN 61557-1 EN 61557-2 EN 61557-5 For installation tester: CAT III 600V For earth resistance tester: CAT IV 400V |