FEATURES
- High quality Taut Band movement
-
Three insulation test voltages(DC): 250V, 500V,1000V
-
Two continuity tests on low ohms: 3Ω & 500Ω
-
Compact and lightweight
-
AC voltmeter with linear scale up to 600 Vac
-
200mA short circuit current for continuity
-
1mA test current on insulation test at nominal voltage
-
Automatic discharge of capacitive and inductive circuit with charge stored in the circuit under test
-
Live warning and display of external voltage presence
-
Fuse, air gap, crowbar and overload protection
-
On line battery monitoring shows if battery is ok
-
Manual zero ohm adjustment
-
Low battery consumption
-
Mirror scale
-
Push and turn locking switch for continuous hands-free testing
-
Designed to meet international standards
-
Supplied with high quality test leads
-
BS 16th edition
SPECIFICATIONS
Insulation Resistance
Test voltage (DC V) |
250V / 500V / 1000V |
---|---|
Output voltage on open circuit | Rated test voltage +10% |
Measuring ranges | 0-100MΩ / 0-200MΩ / 0-400MΩ |
Mid-scale value | 1MΩ / 2MΩ / 4MΩ |
Scale multiplier | ×1/2 / ×1 / ×2 |
Accuracy | ± 5% of indicated value |
Output short- circuit current | ≥1.0mA |
Continuity
Measuring ranges | 3Ω / 500Ω |
---|---|
Output short- circuit current | ≥200 mA |
Accuracy | ± 1.5% of scale length |
AC Voltage
Range | 0-600V AC |
---|---|
Accuracy | ± 3% of scale length |
General
Voltage warning | Live circuit warning light illuminates from 90Vdc / 70Vac; buzzer sounds from 24V ac/dc |
---|---|
Battery check | Battery check position on rotary switch tests batteries from 8Vdc to 10Vdc during load tests of 205mA Battery OK LED also illuminates from 6.5Vdc
and is operative while testing
|
Dimensions | 205(L) × 90(W) × 55(D)mm |
Weight (battery included) |
Approx. 550g |
Power source | 1.5V (AA) × 6 |
Safety standard | EN 61010-1 CAT III 600V EN 61326-1 |