FEATURES

  • Capable of measuring earth resistance and earth voltage.
  • 2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.
  • Auto power off function.
  • The timer operates automatically for about three to five minutes when the "PUSH BUTTON SWITCH" and "TIMER ON BUTTON" are pressed together. This will keep test "ON" for the duration of the timer.
  • Timer for test function (count 3-5 minutes).
  • Battery operated.
  • Data hold function.
  • Small and light weight.
  • Calibration performed with supplied test leads.

SPECIFICATIONS

Measuring ranges Earth resistance
0-20Ω / 0-200Ω / 0-2000Ω
Earth voltage
0-200 Vac (40-500Hz)
Accuracy Earth resistance
±(2%rdg+2dgt) or ±0.1Ω, which is greater
Earth voltage
±(1%rdg+2dgt)
Earth resistance resolution 0-20Ω : 0.01Ω
0-200Ω : 0.1Ω
0-2000Ω : 1Ω
Measuring system Earth Resistance by constant current inverter 820Hz approx. 2mA.
Display 3½ digit (2000 counts)
Open circuit indication LED will be unlit
Low battery indication “ B “symbol appears on the display
Data hold indication “ DH “symbol appears on the display
Over range indication “1”(MSD)
Dimensions 163(L) × 100(W) × 50(D)mm
Weight (battery included) Approx. 480g
Power source 1.5V (AA) × 6