Product Category

1620 ER

Datasheet print icon-img

FEATURES

  • Microprocessor-controlled.
  • Measures earth resistance in three ranges : 40Ω, 400Ω, 4kΩ.
  • Capable of measuring earth voltage.
  • 3 ¾ digit (4000 counts).
  • LCD backlight display.
  • 2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.
  • Data hold function.
  • Relative function.
  • Auto power-off function.
  • Low battery indication.
  • Calibration performed with supplied test leads.

SPECIFICATIONS

Measuring ranges Earth Resistance
0~40Ω / 0~400Ω / 0~4kΩ
Earth Voltage
0~400V (40~500Hz)
Accuracy Earth Resistance ±(2%rdg+3dgt)
Earth Voltage ±(2%rdg+3dgt)
Earth resistance resolution 0~40Ω : 0.01Ω
0~400Ω : 0.1Ω
0~4kΩ : 1Ω
Measuring system Earth resistance by constant current inverter 820 Hz, 2mA approx.
Dimensions 163(L) x 102(W) x 50(D)mm
Weight (battery included) Approx. 440g
Power source 1.5V (AA) x 6
Safety standards EN 61010-1 CAT IV 400V
EN 61326-1
EN 61557-1
EN 61557-5

Feedback list

Post your feedback
Cart

Login

Login Success