FEATURES

  • Measures Insulation Resistance, voltage (AC-DC) measurements
  • Automatic hold facility.
  • Continuity test with a short circuit current of minimum 200mA.
  • MOV and Gas Arrester Testing.
  • Energy conservation is feature.
  • EnerSave™ limits the test duration to about 10 Seconds to save energy.
  • No moving parts. All calibration are saved internally in a non volatile memory.
  • Easy calibration at any facility around the world.
  • Low cost maintenance, calibration, and ownership.
  • Complies to all the latest regulations, including UK.

SPECIFICATIONS

Insulation Test
Test voltage
(DC V)
250V / 500V / 1000V
Output voltage @ 1mA Rated test Voltage +10% Max
Measuring ranges 0.2M~2G / 0.2M-4G / 0.2M-8GΩ
Accuracy 0.2M~4GΩ : ±3%rdg
4GΩ~8GΩ : ±5%rdg
When voltage is constant, Current is limited at 1.2mA
Short circuit current 4mA Max.
Continuity Test
Measuring ranges 0.01-1999Ω
Accuracy 0.01-100Ω : ±1.0%rdg
100-300Ω : ±1.5%rdg
300-1999Ω : ±2.0%rdg
Short circuit current >220mA
Open circuit voltage 5V dc
Resolution ±2 counts
Voltmeter
AC voltage (Auto) 0-700V
DC voltage (Auto) 0-950V
Accuracy ±1.5% rdg
Resolution ±1V
MOV Test & GAS Arrester Test
Test voltage 5-1020Vdc
Voltage result accuracy ±3% rdg
Voltage result resolution ±2 counts
Protections
Over load 700V (between all terminals)
Over voltage Class III-700V towards ground
Fuse 500mA 250V, (5 × 20mm), HBC, Fast Blow
General
Display 2 lines × 16 characters LCD
Auto-null threshold
Buzzer threshold
Fast test 10Sec
Long test 60Sec
With PI and DAR test function 10Min
Load battery test current About 300mA
Operating temperature 0°C to 40°C not in full sun
Storage temperature -10°C to 50°C
Dimensions 250(L) × 190(W) × 110(D)mm
Weight
(battery included)
Approx 1460g.
Power source 1.5V(AA) × 8