FEATURES
- Microprocessor-controlled.
- Very low consumption.
- 50Hz and 60Hz operation.
- Accurate digital readout of disconnection time.
- Over temperature protection.
- Over voltage protection.
- Fuse protection.
- Zero crossing circuitry permit testing at 0° or 180°.
- Auto power off.
- Backlight function.
- Wiring polarity indicator.
- Measure voltage between Line and Earth before testing.
- Frequency measurement indication.
SPECIFICATIONS
| Current Settings | 5mA, 10mA,15mA, 30mA, 50mA, 150mA |
|---|---|
| Current Selection | Rotary Switch Selector |
| Phase Start Selection | Referenced to Earth |
| 0° and 180° | Yes |
| Over-Temperature Protection | Yes |
| Wiring Correctness Indication | Yes ( LEDs ) |
| Trip Indicator | Yes ( LCD ) |
| Operating Voltage ( L-E ) 50Hz or 60Hz | Version A : 240 Vac Version B : 230 Vac |
| Voltmeter (L-E) | 10Vac ~ 280Vac (50Hz or 60Hz) |
| Timer Resolution | 1ms (Max Time = 2.999s) |
| Timer Accuracy | ± 2ms |
| Current Accuracy | ± 5% ± 1mA |
| Voltmeter Resolution | 1Vac |
| Voltmeter Accuracy | ± 2%±1Vac |
| Operating Temperature | 0°C ~ 40°C |
| Storage Temperature | -10°C ~ 50°C |
| Dimensions | 175(L)×85(W)×75(D)m |
| Weight (batter included) | Approx. 660g |
| Power source | 1.5V (AA) × 8 (Alkaline battery) |
| Safety standard | EN 61010-1 CAT IV 300V EN 61326-1 |


Feedback list