Product Category

1826 NA

Datasheet print icon-img

FEATURES

  • Microprocessor-controlled.
  • Measures Earth Resistance without the need for poles in the ground or external measuring wires.
  • Earth measurement uses the real earth current path and the current generated by the electric network, without the need for any disconnection.
  • The Earth Resistance displayed is exactly the earth resistance that the earth current will need to go through if an earth fault occurs. No need to add all the bonding points and connection paths resistances.
  • Displays voltage supply at the transformer (Line to Neutral), without loading the transformer.
    Displays voltage between Line (Phase) and Earth (Ground), without drawing any current.
  • Measures the impedance of the line itself so you can analyze and differentiate between the multiples paths of the wiring.
  • Measures the Neutral Impedance.
    Single one smart push button operation; ON, Test, Scroll trough results and menus.
  • Checks wiring integrity (LEDs).
  • Auto off/auto ranging (software ranging).
  • Combined prospective short circuit current, loop, individual wire and Earth Tester.
  • Voltage test L-N and L-E.
  • Loop test for L-E and L-N and PSC.
  • Enables analysis of constituent components in L-E and L-N loops giving resistance of earth, neutral wire, live wire and transformer winding.
  • Display can be customized for large orders.

SPECIFICATIONS

Loop impedance range L-E, L-N 0.03-2000Ω (software ctrl)
Test currents in each loop 11.76A at 230V / 50Hz
Voltage measurement L-N,L-E 50 to 280V AC (Sine)
Earth wire/path return resistance 0.01-2000Ω (software ctrl)
Neutral wire resistance 0.01-2000Ω (software ctrl)
Line wire resistance & transformer windings 0.01-2000Ω (software ctrl)
PSC current (L-N) max 6kA at 230Vac supply
PSC current (L-E) max 6kA at 230Vac supply
Operating voltage 230V±20V at 50Hz Sine
Loop impedance ±4%rdg ± 2dgt
PSC current ±10%rdg ± 5dgt
Voltage ±2%rdg ±1dgt
Operating-temperature
Operating-humidity
0°C to +40°C 80% Max.
relative humidity
Dimensions 170(L) × 165(W) × 92(D)mm
Weight
(battery Included)
Approx. 970g
Power source 1.5V (AA) × 8
Safety standard EN 61010-1 CAT III 300V
EN 61326-1

Feedback list

Post your feedback
Cart

Login

Login Success