1825 LP

Datasheet print icon-img

FEATURES

  • Microprocessor-controlled.
  • Measures the voltage drop as if 16A was flowing between Line and Neutral.
  • Displays voltage without current (V at 0A).
  • Display voltage as if 16A flowing between Line and Neutral (V at 16A).
  • Loop test for L-E
  • PSC between L-N.
  • Single one smart push button operation; ON, Scroll through results and menus.
  • Checks wiring integrity (LEDs).
  • Auto off/auto ranging (software range).
  • Combined prospective short circuit current, loop and load tester.
  • Display can be customized for large orders.

SPECIFICATIONS

Loop impedance range L-E 0.03-2000Ω (software ctrl)
Test currents in each loop 11.76A at 230V / 50Hz
Voltage measurement L-N 50 to 280V AC (Sine)
Load current for volt drop (L-N) 16A (Calculation)
Neutral wire resistance (Not available, see 1826 NA)
Line wire resistance & transformer windings (Not available, see 1826 NA)
PSC current (L-N) max 6kA at 230Vac supply
PSC current (L-E) max (Not available, see 1826 NA)
Operating voltage 230V±20V at 50Hz Sine
Typical Accuracy
Loop impedance ±5%rdg ± 2dgt
PSC current ±12%rdg ± 5dgt
Voltage ±3%rdg ±1dgt
Operating - temperature
Operating - humidity
-10°C to +40°C 80% Max.
relative humidity
Dimensions 170(L) x 165(W) x 92(D)mm
Weight
(battery included)
Approx. 970g
Power source 1.5V (AA) x 8
Safety standard EN 61010-1 CAT III 300V