Product Category

888 PMR

Datasheet print icon-img

FEATURES

  • Indicates phase rotation.
  • Indicates phase presence.
  • Indicates motor rotation/wiring.
  • Indicates battery status.
  • Phase rotation and motor rotation indication works from as low as 1Vac.
  • Small, rugged enclosure.
  • Color coded test leads.
  • Phase presence indication from as low as 100 Vac.
  • Very low consumption.
  • Fused.
  • Lightweight, robust and compact.
  • Works from 2 Hz to 400 Hz Sine.

SPECIFICATIONS

Phase Presence Nominal Voltage for Phase Presence Indication (The voltage required for the neon Lamps L1, L2, L3 to light up). From To Freq 100Vac
600Vac
10-400Hz
Determination of Phase Rotation Field Direction From To Freq 1Vac
600Vac
2-400Hz
Determination of Motor Connections
(requires > 1/2 turn of the shaft)
From To Freq 1Vac
600Vac
2-400Hz
Maximum Current Consumption 18mA
Over Voltage CLASS III 600V
Over Load between all terminals 600V
Battery OK goes off when battery voltage < 6.5 Vdc
Dimensions 153(L) × 72(W) × 35(D)mm
Weight
(battery included)
Approx. 185g
Power source 9V(6F22) × 1
Safety standard EN 61010-1 CAT III 600V

Feedback list

Post your feedback
Cart

Login

Login Success