Product Category

6221 EL

Datasheet print icon

FEATURES

  • Microprocessor-controlled.
  • Indicates phase rotation.
  • Indicates phase presence.
  • Tests for disconnection sensitivity.
  • Indicates battery status.
  • Tests for disconnection time.
  • Measures voltage phase to earth.
  • Select one of 3 Phase to test ELCB.
  • Color-coded test leads.
  • Phase presence indication from as low as 100Vac.
  • Very low consumption.
  • Fused earth leakage tester.
  • ELCB works 50Vac to 330Vac 50Hz / 60Hz.
  • Led indication of Voltage on ELCB.
  • Phase rotation and presence does not require battery to indicate.
  • EN 61010-1 CAT III 550V. EN 61326-1

SPECIFICATIONS

Determination of the Phase Presence
Nominal Voltage for Phase Presence Indication (the voltage required for the neon lamps L1, L2, L3 to lit up) From 100Vac to 450Vac.
Frequency Range From 10Hz to 400Hz.
Determination of the Phases Rotary Field Direction
Direction (the voltage required to have the direction LEDs L1-L2-L3 or L2-L1-L3 to indicates) From 100 to 450Vac.
Frequency Range From 2Hz to 400Hz.
Protection
Over Load 550V(between all terminals)
Over Voltage Class III - 450V towards ground.
Earth Leakage
Current Settings 999mAac / 50Hz-60Hz
Current Selection Knob
Phase Start Selection(*) 0° and 180°
Over-Temperature Protection(*) Yes
Phase Polarity Trip Indicator(*) Yes
Operating Voltage(L-E) 220Vac to 317Vac
(*)Referenced to Earth
Timer Resolution 1ms(Max. Time = 99.99s)
Timer Accuracy 1ms ± 4ms
Current Accuracy ±3% ± 4mA
Current Resolution 1mA
Voltmeter Accuracy(50Hz) 50-350 Vac = ±3% ± 2V
350-550Vac = ±7% ± 3V
Voltmeter Resolution 1V
Maximum Current Specified at 317Vac / 50Hz
Batteries 1.5V "C" × 8 Alkaline batteries
Bat OK Led = Vbat >9V
Dimensions 330(L) × 260(W) × 160(D)mm
Weight 3850g (batteries included)
Operating temperature Range 0°C to + 40°C
Storage Temperature -10°C to + 50°C